Apc Ups Windows Hyperterminal Software Commands

If you’re looking for a free and solid application to use for your serial COM connections, try PuTTY. It’sfree for commercial and private use, and takes up a mere 444KB of disk space.

Windows Vista and Windows 7 only support the private edition of HyperTerminal. Windows 7 does not even ship with HyperTerminal. The private edition is NOT FREE for commercial use. Its license requires you purchase the application if used commercially, with the cost of the application being US$59.99, as listed on Hilgraeve’s website. In my case its 'APC UPS Service: Event ID: 61455' Using Windows' build in Task Schedule, create new Task and set so that when Event ID 174 is triggered, run execute.bat file. This means that when APC is running on power, it will trigger these scripts. Cd c: Windows System32 bash -c -l '/mnt/c//execute.bat. Trusted Windows (PC) download HyperTerminal 7.0. Virus-free and 100% clean download. Get HyperTerminal alternative downloads. PowerChute Business Edition v9.5 (32 bit systems only) UPS management, graceful shutdown, and energy management software for servers and workstations using dedicated serial or USB connections. We have 8x APC Smart 2200 UPS' with Network Management Cards installed. Is there a centralized server software out there that will allow us to receive alerts when one or all of the UPS' revert to battery backup or fail and that same software issue a shutdown for servers connected to those UPS' without having to configure Powerchute Network Shutdown on each server connected?

The latest PuTTY version can be downloaded here:

Apc Ups Windows Hyperterminal Software Commands

Windows Vista and Windows 7 only support the private edition of HyperTerminal. Windows 7 does not even shipwith HyperTerminal. The private edition is NOT FREE for commercial use. Its license requires you purchasethe application if used commercially, with the cost of the application being US$59.99, as listed onHilgraeve’s website.

To use PuTTY for your serial COM connections, follow these steps:

  1. Figure out the COM port you’ll be using.
  2. Run PuTTY.
  3. Switch the Connection Type to Serial.
  4. Edit the Serial Line to match the COM port you want to use.
  5. Edit the Speed to match the BAUD Rate you want to use.
  6. Select the Serial category from the menu on the left.
  7. Make sure all of the settings are correct (the settings in the screenshot are what I used for mysession, yours could look different depending on what you’re connecting to).
  8. Select the Open button to start the session.

Your connection should now be fully functional.

If you find yourself using PuTTY quite extensively, you could save settings to different profilesfor fast future usage. To create a profile for your settings:

  1. Make sure you have the settings you require.
  2. Enter a profile name under Saved Sessions.
  3. Click the Save button.

On your next PuTTY session, you can load your profile by selecting it from the list and clicking theLoad button.

Logging is also a great feature that PuTTY provides. It lets you output your entire session to a log file. To enable logging, follow these steps before you open your connection:

Apc ups commands hyperterminal

Apc Ups Windows Hyperterminal Software Commands Free

  1. Select Logging from the category list on the left.
  2. Choose your desired logging method (All session output, printable output, etc…)
  3. Enter a file name.
  4. Select the file handling settings.
  5. Open your connection.
Did you know that we also do BACnet Integration Solutions?

Chipkin has BACnet solutions for almost every situation. We have over 20+ years ofexperienceinBACnetintegration, check out our BACnet Products:

The Device IP Configuration utility supplied by APC can also apply IP addresses to NMCs, however, this method is unreliable, often not finding NMCs and when it does, not always successfully applying the IP Address. The below steps cover how to configure the NMC IP address using the serial cable supplied with the card itself.
  • Remove all loads from the UPS.
  • Turn off the UPS (Power button, front panel)
  • Remove mains power from UPS
  • Hold down power button (front panel) for 5 seconds to disconnect battery.
  • Remove back panel where NMC is to be installed.
  • Install NMC
  • Plug UPS back into mains
  • Connect Serial cable that came with NMC
  • Attach to laptop
  • Download and run PuTTY – Telnet Client (or any alternative)
  • Connect with the following settings
    • Bits per second 9600
    • Data Bits 8
    • Parity None
    • Stop bits 1
    • Flow Control None
  • Connect and press enter until you are prompted for a username
    • Username: APC
    • Password: APC
  • Set IP Address using the following commands;
    • apc> tcpip -iyourIPaddress-syourSubnetMask -gyourDefaultGateway
    • apc> reboot

Apc Ups Windows Hyperterminal Software Commands List

Example;
apc>tcpip-i159.216.45.39-s255.255.254.0-g159.216.45.1

Apc Ups Windows Hyperterminal Software CommandsApc ups windows hyperterminal software commands download
The NMC will now reboot and the IP address should be configured. To test, browse to the IP Address and see if the NMC web interface loads.